SKAS – Sewage Combination Air Release Valve with Valve Chamber
SKAS – Sewage Combination Air Release Valve with Valve Chamber
Spec Sheet: SKAS with Valve Chamber
SKAS with valve chamber-provide the proper solution for those locations requiring cost saving, frost protection, installation under roads, pavements, buildings. The air valve will ensure the proper operation of sewage lines allowing the release of air pockets during working conditions, the evacuation and the entrance of large volumes of air during filling and draining operations.
Functions:
1. Large air release during the filling of the pipeline by anti-shock orifice.
2. Small air release under a pressurized pipeline.
3. Large air intake during draining of the pipeline.
Interested in this product?
Or call +44 7763 488809
SKAS – Sewage Combination Air Release Valve with Valve Chamber
Features:
– Advanced design with a simple mechanism, strong float to prevent cracking during sudden water hammer & quick closure.
– Aerokinetic mechanism to resist blow shut under higher air velocity even up to a sonic air velocity.
– With a special fat body design to lower the sewage water flow speed, and let the air out but keep sewage water underneath.
– Keep dirty or corrosive liquid inside the body for safety during operation and no harm to humans & surrounding environment.
– Internal body guide and upper round wall keep floating on its rail and keep liquid turbulence flowing within this area.
– Much bigger airflow through the nozzle even for higher viscosity liquid.
– Outside screens will be an option for safety and to prevent insects or birds.
– Fully fusion epoxy coated inside and outside valve body for long-term services.
– Manufacturing standard meets or exceeds BS EN 1074-4, AWWA C512
– Flange drilling and dimension meets BS EN 1092 BS EN 558 and ANSI flange.
General Application:
For sewage water system.
Technical Data:
Size Range: DN50
Pressure Ratings: 1.0Mpa,1.6Mp(Thread)
Working Temperature:-10C- 80C
Suitable Media: Sewage Water
Please consult the factory for PN25 and anti-shock device whenever there is a water hammer issue

Technical Specifications
| Size | DN50 |
|---|---|
| Pressure Rating | PN10 / PN16 |
| Temperature Range | -10°C to 80°C |
| Flow Media | Sewage water |
| Body Material | Ductile Iron, fusion epoxy coated |
| Flange Compatibility | BS EN 1092 / ANSI |
| Features | Valve chamber for frost protection and below-ground installation |
To enquire about this product or request a quote, call +44 7763 488809, email john@afcvalves.co.uk, or use our Contact Us page.
Product Specifications
The AFC Valves SKAS Sewage Combination Air Release Valve with Valve Chamber is a complete installation assembly for foul water and sewage pressurised pipelines. It combines an anti-slam air release valve for continuous air venting under pressure with a large orifice kinetic air valve for releasing large volumes of air during pipeline filling and admitting air during draining. The pre-assembled chamber unit simplifies installation on buried rising mains and reduces the risk of incorrect valve selection or assembly on site.
The SKAS is specified on sewage rising mains, pumped sewer systems, and wastewater infrastructure projects managed by water utility asset management programmes and civil contractors in the UK and Ireland. The valve internals are manufactured from materials compatible with sewage and septage service.
Key Specifications
- Size range: DN50 to DN200
- Pressure rating: PN10 / PN16
- Body material: Ductile iron GGG40
- Float material: Polypropylene (PP) or stainless steel
- Seals: EPDM
- End connections: Flanged to BS EN 1092-2
- Standard: BS EN 1074-4 (air valves for liquid pipelines)
- Application: Sewage, foul water, wastewater rising mains